19
WT-9001 IP65 GSM Remote Monitorin
& Remote Control S
stem
COPYRIGHT ©2011
WITURA CORPORATION SDN BHD
N stands for input number 1 – 12 (1 – 4 for Analogue and 5 – 12 for Digital)
X stands for position for 1 - 20 administrators with function value: 0 (OFF), 1 – 9
(number of text alerts)
Example 1:
Any alarm coming from Input 1 will generate 2 SMS to administrators 1, 2, 3 and 1 SMS
to the rest, you would send the following SMS message to the unit.
*RER1#22211111111111111111
Example of Returned Message:
RER1=22211111111111111111 OK
Example 2:
Any alarm coming from Input 2 will generate 3 SMS to administrator 1, 2 SMS to
administrator 2, 3, 4 and 5, no SMS to the rest, you would send the following SMS
message to the unit.
*RER2#32222000000000000000
Example of Returned Message:
RER2=32222000000000000000 OK
To check the setting, you can send the following SMS command to the unit.
*RER?#
The Input Alert Message can be edited and programmed up to 50 characters long. You
can change the displayed text by sending the following commands by SMS message to
the unit.
Note: Only support normal abc/ABC English text, no special characters.
Text Command:
*STR[N]#XXXXX…
N stands for number 5 - 12 of Input
XXXXX… stands for the display text that you want to program. Maximum 50 characters
5.4.8 Editing the Input Alert Message For (When Input gets High Pulse)