Witura WT-9001 IP65 Manual de usuario Pagina 16

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 15
16
WT-9001 IP65 GSM Remote Monitorin
g
& Remote Control S
y
stem
WT-9001 IP65 – USER MANUAL – Rev. 4.7 – Technical Support: [email protected]
COPYRIGHT ©2011
WITURA CORPORATION SDN BHD
Note: This Function Works On Analogue Input Only
There are 4 alarm set points available on each analogue input. It allows the unit to
generate alarms whenever the monitored signal reaches the set point. To program the
alarm set points, you can send the following command by SMS to the unit.
Text Command:
*ALP[N][I]#XX,F
N stands for input number 14
I stands for set point number 14
XX stands for 2 digits Percentage Threshold Alert Value for Alarm
F stands for the perform functions (Selectable) 010
Selectable Functions (F) Description:
Function 0:
No Function
Function 1:
Activates output relay 5 to stay on
Function 2:
Activates output relay 6 to stay on
Function 3:
Activates output relay 7 to stay on
Function 4:
Activates output relay 8 to stay on
Function 5:
Sends a programmable alert message (*SDF[N]#)
Function 6:
Sends a programmable alert message (*SDF[N]#) and activates audible alarm
(Depends on function *ALM#)
Function 7:
Turn off output relay 5. The unit will send SMS if the relay 5 is ON at previous state.
If not it won’t send SMS.
5.4.3 Setting the Alarm Set Points for Analogue Input